A comprehensive technical guide to portable appliance testing (PAT) for London and businesses. Covers the IET Code of Practice, Class I and II appliances, testing methods, pass/fail criteria, risk assessment, frequency guidance and documentation requirements.
PAT testing in the UK follows the IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment (5th Edition, 2020). This document, published by the Institution of Engineering and Technology, provides guidance on: the risk-based approach to testing; testing intervals; methods and procedures; pass/fail criteria; documentation; and the competence required of those carrying out PAT testing.
The Code of Practice is not itself legislation — it is guidance. However, following the Code provides strong evidence of compliance with the Electricity at Work Regulations 1989, the Health and Safety at Work Act 1974, and other relevant legislation. Deviating from the Code without good reason creates legal risk.
The 5th Edition IET Code of Practice emphasises a risk-based approach to determining testing frequency. The key factors are:
Applies to Class I appliances only. Tests the continuity of the protective earth conductor from the plug earth pin to the metal casing of the appliance. The test uses a low DC voltage (typically 200mA or greater) passed through the earth circuit. The measured resistance must be below a specified maximum — typically 0.1Ω + R (where R is the resistance of the supply cord). A result above this threshold indicates a broken or high-resistance earth connection, which is a potential safety hazard.
Applies to Class I and Class II appliances. Tests the integrity of the electrical insulation between the live and neutral conductors and the earth (for Class I) or between live/neutral and the accessible metal parts (for Class II). The test applies a high DC voltage (typically 500V DC) and measures the resistance of the insulation. A minimum acceptable value of 1MΩ is typically required. Lower resistance indicates degraded or damaged insulation — a potential leakage current hazard.
An alternative to the insulation resistance test, particularly suitable for appliances that cannot withstand the 500V DC test voltage (IT equipment, some Class II appliances). Measures the current that flows through a test load connected between accessible parts of the appliance and earth under normal supply conditions. The acceptable limit is typically 0.25mA (portable) or 3.5mA (stationary).
Not required for most routine PAT testing, but recommended for some appliances. The appliance is switched on and allowed to run for a short period under normal operating conditions. This checks that the appliance actually functions and allows the tester to observe any anomalies in operation that might indicate a fault.
The IET Code of Practice requires that records of PAT testing be maintained. Records must include:
We provide all documentation in digital format (PDF and spreadsheet) after every PAT testing visit, suitable for HSE inspection, insurance purposes or HMO licensing compliance.